87211
– GEM250ML5AC3-5
GE HID Distributor Replacement Kit Magnetic Core & Coil Ballast
• Magnetic ballast construction ideal for a wide variety of lighting applications.
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity.
• Distributor replacement kit contains the appropriate core & coil with color coded leads, a properly rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Multi-5 ballast (120, 208, 240, 277, or 480 Volt) featuring a 480-Volt tap.
| GENERAL CHARACTERISTICS |
| Category |
High Intensity Discharge |
| Primary Application |
1- 250w MH M 58 or H 37 Multi-5 small standard frame
|
| Ballast Type |
Magnetic - Core & Coil |
| Type |
Replacement kit |
| Line Voltage Regulation (+/-) |
10 % |
| Ballast Factor |
Normal |
| Circuit Type |
CWA |
| Insulation Class |
180C |
| Enclosure Type |
None |
| Capacitance |
15 µF |
| Capacitor Temperature Rating |
100 °C(212 °F) |
| ELECTRICAL CHARACTERISTICS |
| Supply Current Frequency |
60 Hz |
| Voltage (MIN) |
400.0 |
| PRODUCT INFORMATION |
| Product Code |
87211 |
| Description |
GEM250ML5AC3-5 |
| Standard Package |
Master |
| Standard Package Quantity |
6 |
| Sales Unit |
Distributor Kit |
| No Of Items Per Sales Unit |
1 |
| No Of Items Per Standard Package |
6 |
| UPC |
043168872119 |
|
|
| DIMENSIONS |
| Case dimensions | | Length (L) | 4.0 in (101.60 mm) | | Width (W) | 2.8 in (71.45 mm) | Mounting dimensions | | Bracket Length (BL) | 5.5 in (139.70 mm) | | Mount Length (M) | 3.5 in (88.90 mm) | | Mount Width (X or F) | 2.4 in (61.92 mm) | | Mount Slots (MS) | 0.2 in (4.95 mm) |
| Weight |
9.0 lb |
| Exit Type |
Side |
| Nominal Length |
3.2500 in(82.55 mm) |
| Lead lengths | Qty | Exit | Length (± 1 in.) | | Black | 1 | | 12.0 in (305 mm) | | Black/Yellow | 1 | | 12.0 in (305 mm) | | Orange | 1 | | 12.0 in (305 mm) | | Red | 1 | | 12.0 in (305 mm) | | Violet | 1 | | 12.0 in (305 mm) | | Violet/White | 1 | | 12.0 in (305 mm) | | Yellow | 2 | | 12.0 in (305 mm) |
View Larger
|
| SPECIFICATIONS BY LAMP & LINE VOLTAGE |
| Lamp |
# of Lamps |
Specifications by Line Voltage |
|
M58
|
1 |
|
120 |
208 |
240 |
277 |
480 |
|
|
System Wattage (W) |
280 | 280 | 280 | 280 | 280 |
| Nominal Current |
2.50 A | 1.40 A | 1.25 A | 1.10 A | 0.65 A |
| Ballast Factor |
1 | 1 | 1 | 1 | 1 |
| Ballast Efficiency |
0.893 | 0.893 | 0.893 | 0.893 | 0.893 |
| Drop Out Voltage |
65 V | 105 V | 125 V | 150 V | 260 V |
| Power factor (>=) % |
90 | 90 | 90 | 90 | 90 |
| Min. starting temperature |
-22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 |
| Fuse rating |
8 | 5 | 4 | 3 | 2 |
| |
|
|
|
|
|
|
|
|
H37
|
1 |
|
120 |
208 |
240 |
277 |
480 |
|
|
System Wattage (W) |
280 | 280 | 280 | 280 | 280 |
| Nominal Current |
2.50 A | 1.40 A | 1.25 A | 1.10 A | 0.65 A |
| Ballast Factor |
1 | 1 | 1 | 1 | 1 |
| Ballast Efficiency |
0.893 | 0.893 | 0.893 | 0.893 | 0.893 |
| Drop Out Voltage |
65 V | 105 V | 125 V | 150 V | 260 V |
| Power factor (>=) % |
90 | 90 | 90 | 90 | 90 |
| Min. starting temperature |
-22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 | -22 -22.0 / -30 |
| Fuse rating |
8 | 5 | 4 | 3 | 2 |
| |
|
|
|
|
|
|
|
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 208 | 280.0 | 1.4 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 240 | 280.0 | 1.25 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 277 | 280.0 | 1.1 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 208 | 280.0 | 1.4 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 480 | 280.0 | 0.65 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 480 | 280.0 | 0.65 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 277 | 280.0 | 1.1 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 240 | 280.0 | 1.25 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 120 | 280.0 | 2.5 A | 1.0 | | 90 | | | -22.0 / -30 |
Dimming Levels87211 - l_ProductName The following dimming levels apply when paired with: | Dimming Levels | Line Volts | System Watts | Nom. Line Current | System Ballast Factor | Ballast Efficacy Factor | Power Factor | Crest Factor | THD% | Min. Starting Temp | | 120 | 280.0 | 2.5 A | 1.0 | | 90 | | | -22.0 / -30 |
Safety & Performance
|
cUL Listed |
 |
UL Listed |
Cautions & Warnings
87211 GE HID Distributor Replacement Kit Magnetic Core & Coil Ballast
Warning
- Risk of Electric Shock
- Turn power off before servicing--see instructions.
See list of cautions & warnings.
NOTES
- Kit contains the appropriate core & coil with color coded leads, a properly rated capacitor and ignitor (if required) and all other components required for ballast replacement
|
|
WARRANTY INFORMATION
GE Lighting warrants to the purchaser that each ballast will be free from defects in material or workmanship for period as defined in the attached documents from the date of manufacture when properly installed and under normal conditions of use.
Download full warranty
|
|